Answers to questions in agenda MVD-SC meeting of July 9 1999
(see talk L. Wiggers)
-
Schematics: see the
PLC system and
Temp
System descriptions.
-
rack
and crate space required:both systems are located in the same rack.
-
interlock set by PLC system, not by Temp System: open=set_interlock=error
-
Std's are made for PLC system
and Temp System
-
Variables are described for the PLC system and Temp system in the documentation
described before. Error and Warning (Temp error/Cooling error) messages should
produce yellow box. Update frequency of 5-10 s. Error will be generated as
quick as 0.1 s after the event.
-
Can messages are defined (see above)
-
Histogramming of all variables that are sent; update frequency 5-10 s, storage
of averaged value per 10-15 minutes.
-
Configuration files are stored locally in the system, copies at the host
are required to be able to check in case of errors in reading/writing.
-
Logging of error messages is required, information to be kept for 10 days
or so.
-
No need of putting info in the data stream (no use in data-analysis).