9.9 POWER ISOLATION TRANSFORMERS (Grounding and Shielding Techniques by R. Morrison)
The words isolation transformer
imply a solution to a problem. Just adding a transformer to a problem
rarely works. The problem and the solution must match. An isolation transformer
used in instrumentation usually has one or more electrostatic shields wrapped
around internal coils. This transformer is inside of the equipment and is
not considered a part of the facility. These shields are connected to various
points within the instrument and can control the flow of unwanted current
(see Section 5.6). When an isolation transformer is used to power a group
of instruments, then some new issues arise. The transformer becomes a part
of the facility, and the role of the shields is quite different.
The transformers and associated circuits that are described
in this section can be single-phase or three-phase. The single-phase circuit
is used as an example because it is simpler to draw. The single shield is
shown in Figure 9.1.
This
transformer is ideally mounted on a ground plane. The single shield is internally
connected to the transformer frame. When the transformer is mounted, the
shield is connected. The primary and secondary conductors are carried in
conduit. The conduit bonds to the transformer frame and is considered a part
of the equipment grounding system.
Transformer action involves the difference signal between
the power conductors. There can also be a common-mode signal (interference)
on the primary transmission line. The shield in Figure 9.1 reflects any common-
mode signals and stops them from coupling to the secondary circuits. Without
the shield, capacitance couples common-mode signals directly from the primary
to the secondary circuits. In a typical isolation transformer the leakage
capacitance out of the shield is about 5 pF. With a shield, most of the
common-mode current returns inside the primary conduit and never sees the
secondary circuits.
Some of the common-mode current flows in coils of the primary
.This current flow appears in the secondary by transformer action. To limit
this effect, a second shield can be added to the transformer. This shield
is internally connected to one side of the primary coil. Common-mode current
now flows between the shields not in the coils of the primary. This added
shield is shown in Figure 9.2.
If the secondary
loads generate any common-mode signals, it is desirable to keep these signals
from propagating through the transformer other systems. This path can be
closed by adding a third shield that is again connected to one side of the
secondary coil.
The power isolation transformer has internal shields that
are not available to the user. If they are brought out separately,
they should be connected at the transformer. Connections to remote grounds
are too inductive. These connections make no electrical sense and they violate
the isolation processes.